Applied Inverter series:

  • SUN2000-2/3/3.68/4/4.6/5/6KTL
  • SUN2000-2/3/3.68/4/4.6/5/6KTL-L1
  • SUN2000-3/4/5/6/8/10KTL-M0
  • SUN2000-3/4/5/6/8/10KTL-M1
  • SUN2000-12/15/17/20KTL-M0
  • SUN2000-12/15/17/20KTL-M2
  • SUN2000 33KTL-A
  • SUN2000 36KTL
  • SUN2000 50/60 KTL-M0
  • SUN2000 100 KTL - M1
  • SUN2000 185 KTL - H1


Required additional components:


Inverter
Components
  • SUN2000-2/3/3.68/4/4.6/5/6KTL
  • SUN2000-2/3/3.68/4/4.6/5/6KTL-L1
  • SUN2000-3/4/5/6/8/10KTL-M0
  • SUN2000-3/4/5/6/8/10KTL-M1
  • SUN2000-12/15/17/20KTL-M0
  • SUN2000-12/15/17/20KTL-M2
Smart meter 
SmartLogger3000 (needed if more inverters in the system)
  • SUN2000 33KTL-A
  • SUN2000 36KTL
  • SUN2000 50/60 KTL-M0
  • SUN2000 100 KTL - M1
  • SUN2000 185 KTL - H1
Smart meter 
SmartLogger3000


Configuration instructions:

Inverter
Instruction
  • SUN2000-2/3/3.68/4/4.6/5/6KTL
  • SUN2000-2/3/3.68/4/4.6/5/6KTL-L1
Link

Access the Power Adjustment  screen on the FusionSolar app

  • Select Power adjustment
  • Select Grid-tied point control
  • Select Active Power
  • Change Control mode to Grid-connected with zero power
  • Change Closed-loop controller:
    • Inverter if only 1 inverter in the system
    • SDongle/SmartLogger if more than 1 inverter 
  • Change Limitation mode:
    • Total power – max self-consumption, inverter output = sum of power in each phase, but power injection to grid possible in case of big unbalance of loads.
    • Single-phase –inverter output = 3 x power in the least consuming phase, therefore, no injection at all


  • SUN2000-3/4/5/6/8/10KTL-M0
  • SUN2000-3/4/5/6/8/10KTL-M1
Link
  • SUN2000-12/15/17/20KTL-M0
  • SUN2000-12/15/17/20KTL-M2
Link



 



Inverter
Instruction
  • SUN2000 33KTL-A
  • SUN2000 36KTL
  • SUN2000 50/60 KTL-M0
  • SUN2000 100 KTL - M1
  • SUN2000 185 KTL - H1

Link

Notice that for the big commercial and utility-scale system the specific solution for Zero Feed-In will depend on the system design. Please contact us for further support.